Inta lagu jiro habka tijaabinta transformer-ka, injineer koronto ahaan, waxaa laga yaabaa inaan la kulanno dhibaatooyin kala duwan inta lagu jiro hawlgalka. Su'aalaha iyo jawaabaha soo socda ee ku saabsan cabbirka CT PT, waxaan ku heli karnaa aqoon iyo macluumaad aad muhiim u ah.
FAQ 1: Waa maxay Khaladaadka saamiga, maxayse 0.2s Class CTs ugu adag yihiin?
Q: Khaladka saamiga 0.05%? Muxuu mitirka CT ugu baahan yahay inuu aad uga saxsan yahay CT-ga ilaalinta?
A: Khaladka saamigu waa % faraqa u dhexeeya saxanka magaca iyo cabbirka . 0.2 macnaheedu waa saxnaanta "gaar ah" ilaa 1% hadda. Waxay ku saabsan tahay "daacadnimada" biilka korontada.
FAQ 2: Polarity - "Veto" ee Ilaalinta Kala Duwan
Q: Maxaa dhacaya haddii saamigaygu kaamil yahay laakiin polarity (S1/S2) la rogo?
A: Nadaamka ilaalinta waxa uu gaysan doonaa "is-dil." Gudbintu waxay arki doontaa khalad wayn oo hadda jira.
Macquul Kala Duwan (87 Relay):
• Fogaanta Saxda ah: 100A gudaha - 100A baxay=0 Farqiga ✅
• Polarity Rooneed: 100A gudaha - (-100A Out)=200Farqi. ❌
Natiijada: Safar been ah oo degdeg ah. Ma awoodsiin kartid saldhigga.
FAQ 3: Barakaca Wajiga (Cillad xagal) iyo biilka Korontada
Q: Maxay tahay sababta "qaladka marxaladda" yar (tusaale{1}}daqiiqo) muhiim u yahay haddii cabirku sax yahay?
A: Sababtoo ah Awood Firfircoon P=V * I * cos(phi). Barakaca wejigu waxa uu beddelaa wakhtiga hirarka hadda socda.
Dabin Sax ah:
Mitiradu waxay cabbiraan xagasha u dhaxaysa V iyo I.
• Markay hooseeyaan-awood-culaysyada factor (tusaale cos phi=0.5), 15-daqiiqo khaladku waxa uu keenaa 1% khalad xaga awooda ah.
FAQ 4: Habka qaabaynta - xaqiijinta 1000A oo leh 120V kaliya
Q: Tijaabooyin dhaqameed ayaa riixaya 1000A ilaa heerka koowaad. Sidee buu falanqeeyaha u noqon karaa mid sax ah la'aanteed?
A: Waxay isticmaashaa "Habka Modeling." Waxay kala saartaa joomatari jireed (rogid) iyo khasaaraha birlabeedka.
Sida ay u shaqeyso:
❶ Qiyaasta leexashada: Sare{0}} buundada korantada saxda ah waxay cabbirtaa Ns/Np.
❷ Qaabka magnetic: qalooca xamaasadda ayaa si sax ah u qabta inta ay le'eg tahay inta ay le'eg tahay xudunta birta ee "xada."
❸ Saadaasha Xisaabta: Kombuyuutarku wuxuu isku daraa leexashada + khasaaraha + culayska si loo saadaaliyo khaladka 1000A.
FAQ 5: Isku halaynta goobta - 0.1% saxnaanta goob buuq badan
Q: Faragelinta substation-ku miyaanay burburinayn cabbirka saxda ah ee 0.1%?
A: Falanqeeyayaasha waxay adeegsadaan Narrow{0}} Kooxda Shaandhaynta Dijital ah iyo Soo noqnoqoshada si ay u aamusaan.
Xeeladaha Diidmada Sawaxanka:
Isbeddelka soo noqnoqda: Wuxuu duraa calaamadaha 49.7 Hz ama 50.3 Hz. Wuxuu iska indhatiray 50 Hz dhawaaqa asalka ah.
Tixraaca Gudaha: Nafta -Waxay ku cabbiraysaa ultra{1}} tixraacyada danab gudaha ee deggan.
• Kelvin 4-Wire: Waxa ay meesha ka saartaa iska caabinta tijaabooyinka tijaabadaada.