Si loo hubiyo badbaadada iyo isku halaynta fiilooyinkan. Waa lagama maarmaan in loo hoggaansamo heerarka tijaabada gaarka ah iyo hababka soo-saareyaasha fiilooyinka si ay u sameeyaan tijaabiyaha aqbalaadda warshadda. Waxaan sahamin doonaa heerarka imtixaanka iyo hababka loogu talagalay xadhkaha korantada ee hooseeya -
Heerarka imtixaanka ugu weyn
Ugu horrayn, waa lama huraan in la fahmo heerarka imtixaanka sida caadiga ah loo isticmaalo xadhkaha korantada ee hooseeya-
Heerarka caalamiga ah
1. IEC 60502: Lagu dabaqi karo fiilooyinka korantada ee leh danab lagu qiimeeyay min 1kV ilaa 30kV, waxay dabooshaa shuruudaha sida dhumucda dahaarka, caabbinta kirishbooyada, iyo u adkeysiga tijaabooyinka tamarta.
2. IEC 60227: Xadhkaha dahaarka leh ee polyvinyl chloride ee leh danab 450/750V iyo ka hooseeya, waxay qeexaysaa shuruudaha sida sii wadida kirishbooyada iyo guryaha farsamada.
3. IEEE 400: Hagaha Tijaabada Goobta ee Xadhkaha Korontada, xooga saaraysa Tijaabada Korantada DC iyo Cabbirka Sababta Khasaaraha Korontada
Habka baaritaanka ugu weyn
Marka ay timaado tijaabinta xadhkaha korantada yar -, waxa jira dhowr habab oo muhiim ah oo sida caadiga ah la isticmaalo.
1. Tijaabada iska caabinta dahaarka
Habka: Isticmaal ohmmeter (qiyaastii 500V ama 1000V) si aad u cabbirto iska caabbinta u dhaxaysa kaari iyo lakabka gaashaanka (Ka weyn ama la mid ah 100 MΩ · km).
Heerka: Marka loo eego GB/T 3048.5-2007, wakhtiga imtixaanku waa 1 daqiiqo, hagaajinta heerkulka deegaanka ayaa loo baahan yahay.
2. U adkaysta Tijaabada Korantada
Inta jeer ee Korontada U adkeysiga Voltage: Codso 2.5U₀ + 2kV (U₀ waa danabka la qiimeeyay) 5 daqiiqo iyada oo aan la burburin (sida ku cad GB/T 3048.8).
Voltage adkeysi DC: Ku habboon fiilooyinka duugga ah, oo leh danab dhan 4 ilaa 6 jeer U₀, laakiin waxa ay dedejin kartaa gabowga dahaarka waana in si taxaddar leh loo isticmaalo.
3. Dheecaan qayb ka mid ah (oo lagu dabaqi karo fiilooyinka korantada dhexdhexaadka ah iyo kuwa sarreeya): Codso danab dhan 1.5U₀, qadarka dheecaanku waa inuu ka yar yahay ama la mid yahay 10pC (IEC 60885-3).