Waa maxay saldhigga doorashada korantada tijaabada ee tijaabada AC Hipot?
Korontada tijaabada waxaa lagu go'aamiyaa heerka dahaarka lagu qiimeeyay qalabka (Um, BIL) iyo heerka sheyga lagu dabaqi karo - ma jiro hal danab caalami ah.
Xulashada korantada ee nooca qalabka:
|
Qalabka |
Heerka |
Tijaabi Voltage |
Muddada |
|
Beddelka Korontada (Um in ka yar ama la mid ah 72.5 kV) |
IEC 60076-3 |
1.7 × Um / √3 (lagu keenay) + PD |
30 s ee imtixaanka + 5 daqiqa Um/√3 |
|
Beddelka Korontada (Um> 72.5 kV) |
IEC 60076-3 |
1.7 × Um / √3 (gaaban -mudada la kiciyay) |
60 s |
|
Beddelka Qaybinta |
IEC 60076-11 |
2.0 × danab lagu qiimeeyay |
60 s |
|
Xargaha Korontada (MV) |
IEC 60502-2 |
2.5 × U₀ |
30 daqiiqo (aqbal) / 60 daqiiqo (inta badan) |
|
Xargaha Korontada (HV) |
IEC 60840 |
2.0 × U₀ |
60 daqiiqo |
|
GIS / Qalabka beddelka |
IEC 62271-1 |
1.2 × Um |
60 s |
|
Bushing |
IEC 60137 |
1.2 × Um (tijaabada PF) |
60 s |
|
CT/VT |
IEC 61869-1 |
1.3–1.5 × Um/√3 (lagu keenay) |
60 s |
Hagaha goobta wax ku oolka ah:
Had iyo jeer la tasho taarikada magaca (liiska Um, BIL).
• Iska yaree danabka 80% ee tijaabada goobta ee qalabka da'da (IEEE 400.2 ee fiilooyinka).
Weligaa ha dhaafin taarikada BIL.
Hubi heerka sheyga ka hor intaadan dooran danab - Transformer vs.