Sidee loo go'aamiyaa tamarta tijaabada AC Hipot ee qalab kala duwan?

 May 18, 2026

 Fariin ku dhaaftid

 

Waa maxay saldhigga doorashada korantada tijaabada ee tijaabada AC Hipot?

Korontada tijaabada waxaa lagu go'aamiyaa heerka dahaarka lagu qiimeeyay qalabka (Um, BIL) iyo heerka sheyga lagu dabaqi karo - ma jiro hal danab caalami ah.

 

Xulashada korantada ee nooca qalabka:

Qalabka

Heerka

Tijaabi Voltage

Muddada

Beddelka Korontada (Um in ka yar ama la mid ah 72.5 kV)

IEC 60076-3

1.7 × Um / √3 (lagu keenay) + PD

30 s ee imtixaanka + 5 daqiqa Um/√3

Beddelka Korontada (Um> 72.5 kV)

IEC 60076-3

1.7 × Um / √3 (gaaban -mudada la kiciyay)

60 s

Beddelka Qaybinta

IEC 60076-11

2.0 × danab lagu qiimeeyay

60 s

Xargaha Korontada (MV)

IEC 60502-2

2.5 × U₀

30 daqiiqo (aqbal) / 60 daqiiqo (inta badan)

Xargaha Korontada (HV)

IEC 60840

2.0 × U₀

60 daqiiqo

GIS / Qalabka beddelka

IEC 62271-1

1.2 × Um

60 s

Bushing

IEC 60137

1.2 × Um (tijaabada PF)

60 s

CT/VT

IEC 61869-1

1.3–1.5 × Um/√3 (lagu keenay)

60 s

 

Hagaha goobta wax ku oolka ah:

Had iyo jeer la tasho taarikada magaca (liiska Um, BIL).

• Iska yaree danabka 80% ee tijaabada goobta ee qalabka da'da (IEEE 400.2 ee fiilooyinka).

Weligaa ha dhaafin taarikada BIL.

Hubi heerka sheyga ka hor intaadan dooran danab - Transformer vs.

U dir sooji
U dir sooji