Sidee waxtarka transformerka looga xisaabiyaa cabbirada khasaaraha

May 19, 2026 Fariin ku dhaaftid

Q: Marka la eego P₀ iyo Pₖ imtixaannada, sidee baan u xisaabiyaa waxtarka heerarka kala duwan ee culeyska?

 

A: Hufnaanta η=P_out / (P_out + P₀ + ² × Pₖ) × 100%, halkaasoo=qodobka rarka.

Tusaale: 10 MVA Transformer, P₀=12 kW, Pₖ=85 kW:

raran

Wax soo saarka (kW)

P₀ (kW)

²×Pₖ (kW)

η (%)

25%

0.25

2,500

12

5.3

99.31

50%

0.50

5,000

12

21.3

99.34

75%

0.75

7,500

12

47.8

99.21

100%

1.00

10,000

12

85.0

99.04

120%

1.20

12,000

12

122.4

98.89

Waxtarka ugu badan=√(P₀ / Pₖ)=0.376 → ~37.6% culeyska

Heerarka waxtarka tamarta:

• IEC 60076-20: EEI fasalada A (ugu sarreeya) → D.

• Ecodesign EU 2019/1783: Tier 2 (2021), Tier 3 (2025-27).

• DOE 10 CFR Qaybta 431: xeer cusub oo dhaqan galaya Juun 2026.

• GB 20052-2020 (Shiinaha): Fasalka 1 (ugu sarreeya) → 3.

IS 1180 (Hindiya): Qiimaynta Xiddiga BEE 1-5.

Habka TCO: TCO=Qiimaha + A × P₀ + B × Pₖ

A ≈ $3,000–8,000/kW (maya - rarida qiimaha weyn).

B ≈ $500–2,000/kW