S: Waxaan u baahanahay inaan tijaabiyo xadhig 220 kV ah, dhererkiisu yahay 8 km. Waa maxay qiimaynta SR ee aan u baahanahay?
A: Habka cabbirida 7-tallaabo: go'aami shuruudaha imtixaanka → xisaabi C → qiyaas L → xisaabi f_res → xaqiiji qiimeynta → dib u habeyn → dhamaystir.
Tallaabo - qaado -tallaabo - 220 kV cable, 8 km:
1. IEC 60840: V_tijaabada=2.0 × 127 kV=254 kV. Muddada 60 daqiiqo.
2. C ≈ 8 km × 0.2 μF/km=1.6 μF.
3. Tixgeli 3× 100 kV/2 A reactors barbar socda: L=26.7 H, f=24.4 Hz.
4. Hadda oo jooga 254 kV: I=V × 2πf × C=6.9 A. Laakin 3×2A → 6A wadarta → MA OK.
5. Kor u qaad 3× 100 kV/4 A reactors: wadarta I=12 A → OK. P_in=254×6.9/35=50 kW.
6. Wadarta miisaanka: 3×450 kg + 200 + 150 + 100=~1,800 kg.
Soo koobidda cabbirka xaaladaha guud:
|
Muuqaal |
V_tijaabada (kV) |
C (μF) |
f (Hz) |
Nidaamka lagu taliyay |
|
33 kV fiilo, 3 km |
48 |
0.6 |
45 |
60 kV/2A ×1, 5 kW |
|
110 kV cable, 5 km |
160 |
1.0 |
24 |
200 kV/4A ×2, 20 kW |
|
220 kV fiilo, 8 km |
254 |
1.6 |
24 |
300 kV/4A ×3, 50 kW |
|
400 kV fiilo, 5 km |
330 |
1.0 |
48 |
400 kV/2A ×2, 25 kW |
|
GIS 245 kV, 10 bays |
230 |
0.05 |
80 |
300 kV/1A ×2, 5 kW |
|
Koronto dhaliyaha 100 MVA |
28 |
2.5 |
45 |
30kV/5A, 10kW |
Xusuusin muhiim ah:
• +20% margin ee qiimaynta korantada reactor . +30% margin ee qiimaynta hadda.
• Haddii P_in> 100 kW, tixgeli baaritaanka qaybta (oo ay ogol yihiin heerarka badankood).
• Dhab ahaantii Q waxa laga yaabaa in uu ka hooseeyo inta la qiyaasay - qorshaynta muxaafidka ahi waxa ay ka fogaataa guuldarada goobta.