Habka cabbiraadda beddelka hadda (CT)

 Dec 17, 2024

 Fariin ku dhaaftid

 

Omicron-ka la rari karo CT{{0}Analyzer wuxuu sameeyaa xamaasad, saamiga, iyo hubinta kala-duwanaanshaha taransfoorayaasha hadda jira iyadoo la adeegsanayo korontada{1}qaabka isbarbardhigga. Transformers hadda waxaa lagu tijaabin karaa qaabeynta qalabkooda, sida in lagu sameeyo transformers, wareegyada saliida, ama qalabka bedela. Waa lama huraan in qalabku si buuxda looga go'doomiyo qalabka korontada ka hor inta aan la tijaabin.
Tijaabada Polarity
Marka lagu xidho dabaylaha tamarta sare leh, farsamada la isticmaalay waxa lagu fulin doonaa iyada oo la shidinayo sahayda hadda jirta ee DC si kooban. Polarity-ka waxaa lagu eegi karaa voltmeter polaized, oo ku xiran dabaysha sare (dhinaca danab hoose). Voltmeter-ka waa in la cabbiraa si loo helo in leexashadu sax tahay.
Caadi ahaan, iska caabiyaha ururinta ayaa lagu isticmaalaa wareegga si loo difaaco qalabka. Haddii cirifka taransfooriyuhu uu sax yahay, leexashadu waa in ay ahaataa isla koorsada marka hadda DC la shido.
Tijaabada Dheefta
Cabbiraadda korantada kicinta iyo hadda kicinta ee saameeya marka korantada loo isticmaalo CT-ga tijaabada hoose uu kordhay. Marka CT-ga ka hooseeya tijaabada uu bilaabo inuu buuxsamo, weyn oo la sameeyay maanta ayaa lagu ogaan doonaa ballaarin yar oo danab ah. Tijaabadaan, qalooca magnetization-ka iyo sifooyinka magnetization-ka ayaa lagu xaqiijin doonaa. Jeega buuxinta waa in la sameeyaa ka hor inta la eegayo saamiga iyo ka dib baaritaanka polarity, iyadoo la arkayo in magnetism-ka haraaga ah uu ku haray xudunta u ah tijaabada DC (polarity, iska caabin), taas oo horseedaysa qalad dheeraad ah oo ku yimaada imtixaanka saamiga.
Imtixaanka saamiga
Hubinta saamiga waxa lagu fuliyaa iyadoo la qiimaynayo korantada ay isticmaasho dabaysha labaad ilaa danabka soo socda ee lagu soo saaray dabaylaha muhiimka ah. Tusaale ahaan, haddii 1 volt per flip loo isticmaalo dabaysha labaad, danab ka jira dabaylaha muhiimka ah wuxuu noqonayaa 1 volt. Si gaar ah, haddii 120V la isticmaalay ilaa heerka labaad ee 600/5 transformer hadda (120:1 ratio), 1V wuxuu u baahan yahay inuu hadda ku jiro
dabaylaha aasaasiga ah

U dir sooji
U dir sooji