S: Megger-kaygu wuxuu leeyahay 500V, 1000V, 2500V, 5000V, iyo 10kV. Kee baan u dooranayaa LV, MV, iyo HV?
A: Codsashada danab aad u yar ma dhibayso dahaarka. Wax badan ayaa sababi kara feer wax duminaya{1}} Raac miiska u dhigma.
Tijaabada Heerka Korantada ee DC:
| Xadhkaha La qiimeeyay Korantada (U0/U) | Heerka dahaarka | Tijaabada Korantada ee DC ee lagu taliyay | Xadka Badbaadada (Max) |
| Korantada Hoose (LV) <0.6/1 kV | Voltage hooseeya | 500V ilaa 1000V DC | 1000V DC |
| Voltage dhexdhexaad ah (MV) 6/10 ilaa 20/35 kV | Voltage dhexdhexaad ah | 2500V ama 5000V DC | 5000V DC |
| Korontada Sare (HV) 66 ilaa 220 kV+ | Korantada Sare | 5000V ama 10,000V DC | 10,000V DC |
Maxaad DC ugu isticmaashaa IR? Sahayda DC si joogto ah uma sawirto dallacaadda awoodda leh dhawrka ilbiriqsi ee ugu horreeya ka dib, taasoo u oggolaanaysa cabbirka dareeraha yar ee iska caabbinta ah ee hadda (micro{0}}amps) ee ku qulqulaya dahaarka.