S: Waa maxay rarka luminta, maxaa sababa, sideese loo cabbiraa?
A: Load luminta (Pₖ) waa awooda ku baab'day dabaylaha dabaylaha awgood culayska hadda socda iyo qulqulka qulqulaya, oo u dhiganta I².
Qaybaha rarka luminta:
• Khasaaraha I²R (~70-85% ee Pₖ) - Kuleylka Joule iska caabinta DC.
• Khasaarida hadda jirta ee dabaysha (~10-20%) - maqaarka + saamaynta u dhowaanshaha.
• Luminta qalooca ee qaybaha dhismaha (~5-10%) - taangiga, xajinta, boolasha xudunta u ah.
Habka Tijaabada - Gaaban - Tijaabada Waxyeelaynta Wareega:
|
Talaabada |
Ficil |
Xusuusin |
|
1 |
Gaaban - wareegga labaad (dhinaca LV) |
Adeegso baararka gaaban ee culus- |
|
2 |
Codso danab yaraaday xagga hoose |
Ka bilow eber; korodhka hadda la qiimeeyay |
|
3 |
Cabbir Vₖ, Iₖ=I_rated, Pₖ |
Vₖ caadi ahaan waa 5-15% Uₙ |
|
4 |
Diiwaangeli Vₖ%=Vₖ / Uₙ × 100% |
Boqolkiiba korantada impedance |
|
5 |
Sax Pₖ ilaa 75 digrii |
Pₖ(75) = Pₖ(T) × (235+75)/(235+T) |
Pₖ aan caadi ahayn ayaa tilmaamaysa:
• > +15% ee la dammaanad qaaday → sare-isku xidhka iska caabinta, xadhig jaban, tabo khaldan
• Kor u kacaya → kobcinta xidhiidhada dabacsan, qallooca dabaysha (eddies).
Vₖ% isbedelay> ± 10% → dabaysha qalloocan (xadka IEC).
Ogolaanshaha: Pₖ In ka yar ama la mid ah dammaanadda + 15% ee 75 darajo; Vₖ% gudaha ± 10% ee dammaanadda.