Waa maxay rarka luminta (luminta naxaasta), sideese loo cabbiraa?

 May 19, 2026

 Fariin ku dhaaftid

 

S: Waa maxay rarka luminta, maxaa sababa, sideese loo cabbiraa?

 

A: Load luminta (Pₖ) waa awooda ku baab'day dabaylaha dabaylaha awgood culayska hadda socda iyo qulqulka qulqulaya, oo u dhiganta I².

 

Qaybaha rarka luminta:

• Khasaaraha I²R (~70-85% ee Pₖ) - Kuleylka Joule iska caabinta DC.

• Khasaarida hadda jirta ee dabaysha (~10-20%) - maqaarka + saamaynta u dhowaanshaha.

• Luminta qalooca ee qaybaha dhismaha (~5-10%) - taangiga, xajinta, boolasha xudunta u ah.

 

Habka Tijaabada - Gaaban - Tijaabada Waxyeelaynta Wareega:

Talaabada

Ficil

Xusuusin

1

Gaaban - wareegga labaad (dhinaca LV)

Adeegso baararka gaaban ee culus-

2

Codso danab yaraaday xagga hoose

Ka bilow eber; korodhka hadda la qiimeeyay

3

Cabbir Vₖ, Iₖ=I_rated, Pₖ

Vₖ caadi ahaan waa 5-15% Uₙ

4

Diiwaangeli Vₖ%=Vₖ / Uₙ × 100%

Boqolkiiba korantada impedance

5

Sax Pₖ ilaa 75 digrii

Pₖ(75) = Pₖ(T) × (235+75)/(235+T)

 

Pₖ aan caadi ahayn ayaa tilmaamaysa:

• > +15% ee la dammaanad qaaday → sare-isku xidhka iska caabinta, xadhig jaban, tabo khaldan

• Kor u kacaya → kobcinta xidhiidhada dabacsan, qallooca dabaysha (eddies).

Vₖ% isbedelay> ± 10% → dabaysha qalloocan (xadka IEC).

Ogolaanshaha: Pₖ In ka yar ama la mid ah dammaanadda + 15% ee 75 darajo; Vₖ% gudaha ± 10% ee dammaanadda.

U dir sooji