Tijaabi heerka 132KV GIS
Qodobka 6.3.4 ee IEC 62271 -1:2017 "Shuruudaha Guud ee Bedelida Voltage Sare iyo Qalabka Xakamaynta" waxay si cad u sheegaysaa in qalabka leh danab lagu qiimeeyay 123 kV (qiimaha lagu qiimeeyay inta badan 132 kV) waa inay buuxiyaan 230 kV tamarta soo noqnoqda iyo 550 kV. IEC 62271-200 sidoo kale waxay kabaysaa oo qeexaysaa xirida gaaska gaarka ah iyo shuruudaha tijaabada dheecaanka qaybeed ee GIS.
Korantada tijaabada AC ee u adkaysata danabka GIS (Gaas Insulated Switchgear) waa in uu u hoggaansamaa "Heerka Imtixaanada Oggolaanshaha ee Qalabka Korantada ee Mashruucyada Rakibaadda Korontada" (GB50150-2016) iyo "Hagayaasha Goobta{2}}U adkaysiga Korantada iyo Dahaarka Qalabka beddelka (DL/T555-2004). Guud ahaan, tamarta tijaabada aqbalka warshadu waa 80% ee tamarta tijaabada warshadda (xaalad gaar ah sida shuruudaha Tallaabooyinka ka hortagga shilalka ee Grid, waxaa laga yaabaa in la kordhiyo ilaa 100%, laakiin tani maaha xaalad caadi ah).
Danab la qiimeeyay (Uₙ) ee 132kV GIS waa 132kV, iyo danab hawlgalka ugu badnaan (Uₘ) waa qiyaastii 145kV (sida GB156-2017 "Standard Voltage", ugu badnaan danab hawlgalka u dhiganta 132kV waa 145kV).
Marka loo eego heerka, korantada tijaabada warshadda (Uₜₑₛₜ) badanaa waa 1.8-2.0 jeer ugu badnaan tamarta hawlgalka (heerar kala duwan ayaa laga yaabaa inay waxyar kala duwanaadaan), iyo tamarta tijaabada aqbalka warshadu waa 80% qiimaha warshadda.
Qaadashada ugu badnaan tamarta shaqaynta ee 1.86 tusaale ahaan (tixraac qiimaha 110kV GIS: ugu badnaan tamarta shaqaynaysa 110kV waa 126kV, iyo tamarta tijaabada warshaduna waa 230kV=126 × 1.86):
Korontada tijaabada warshadda:
U warshad=145 × 1.86 ≈ 270 kV (qiimaha wax ku ool ah, 1 daqiiqo)
Korantada tijaabada komishanka:
U diraya=270 × 0.8=216 kV (qiimaha wax ku ool ah, 1 daqiiqo)