Sahami aqoonta ku saabsan tijaabada soo daynta patial ee korontada

 Aug 21, 2026

 Fariin ku dhaaftid

 

Q1: Waa maxay sababta soo noqnoqda labanlaabmidda (150Hz ilaa 200Hz) ay qasab ku tahay tijaabinta PD ee la kiciyay ee 40 MVA Transformer?

J: Marka la tijaabinayo dahaarka dhaadheer ee taransfooriyaha (-wareega iyo dhexda{1}}lakabka), waxaanu isticmaalnaa danab aad uga sareeya qiimaha la qiimeeyay (sida caadiga ah 1.5x). Haddii aan isticmaalno isha caadiga ah ee 50Hz/60Hz, xudunta birta waxay isla markiiba geli doontaa saturation magnetka, taasoo keenaysa xamaasadda hadda jirta inay sare u kacdo oo ay suurtogal tahay inay burburiso dabaylaha. Marka loo eego qaacidada magnetic flux (Φ=U/4.44fNΦ=U/4.44fN), anagoo kordhinayna inta jeer ee ilaa 150Hz ama 200Hz, waxaanu ku guulaysan karnaa tamarta tijaabada sare anagoo ilaalinayna qulqulka xudunta u ah badbaado, aan{13}}heer saturated ah.

 

Q2: Sideen ku gaari karnaa heerka dhawaaqa asalka ah ee <10pC inta lagu jiro goobta tijaabada 66kV

J: Helitaanka qayladan hoose ee jawiga garoonku waxay u baahan tahay hab habaysan:

Shaandhaynta Hardware: Isticmaalka Isha Awoodda Soo noqnoqota ee Isbeddelka leh oo leh isku-dhafan culus - shaandhaynta LC-ga waajibka si ay u xannibto sare - qaylada soo noqnoqda ee beddelka IGBT.

Hagaajinta Goobta Korantada: Ku rakibida 66kV ee baadiyaha 66kV si loo baabi'iyo koronto-dhalmeed weyn - dhexroor Grading Shield (Corona Ring)

Logic Grounding: Hirgelinta hal -nidaamka dhulka dhigista xidigta si looga hortago wareegyada dhulka ee u shaqeeya anteenooyinka EMI.

Fiilo: Isticmaalka xadhkaha cabbiraadda labajibaaran - si looga ilaaliyo calaamadaha PD ee xasaasiga ah faragelinta jawiga

 

Q3: Waa maxay shuruudaha gudbinta/fashilka ee tijaabada 66kV Transformer PD sida waafaqsan IEC 60076-3?

J: Transformers leh Um =72.5 kVUm=72.5 kV (66kV class), heerku guud ahaan wuxuu u baahan yahay in muddada dheer{3}}kormeeraha korantada ee muddada dheer (sida caadiga ah 1.5Um/31.5Um/3), heerka Bixinta Qaybtu waa inuu ahaadaa ka hooseeya 100pC. Muhiimad ahaan, isbeddelka PD waa inuu ahaadaa mid deggan; koror kasta oo joogto ah ee xajmiga dheecaanka ama heerka garaaca garaaca inta lagu jiro muddada tijaabada 30-60 daqiiqo waxaa loo arkaa mid guuldarreystay, xitaa haddii qiimaha saxda ah uu ka hooseeyo 100pC.

 

Q4: Ma isticmaali karaa isbedbedelka Imtixaanka Hipot-ka AC ee caadiga ah halkii aan ka isticmaali lahaa Nidaamka Soo noqnoqoshada Isbeddelka ah?

A:Transformer dhaqameed ayaa samayn karaTijaabada adkaysiga isha goonida ah(dahaarka ugu weyn ee dhulka). Si kastaba ha ahaatee, waakuma haboonakuwa ka sii daranTijaabada Korantada ee la KeenayCutubka 40MVA sababtoo ah ma bixin karto inta jeer ee la kordhiyay (150Hz+) si looga fogaado buuxinta xudunta u ah. Intaa waxaa dheer, transformers-ka dhaqameed aad bay u culus yihiin oo ay adagtahay in loo qaado saldhigyo 66kV ah oo fog marka la barbar dhigo hababka Frequency Variable modular.

 

Q5: Waa maxay faa'iidada isticmaalka maktabadda faraha ee 2D/3D PRPD ee software-ka ogaanshaha?

J: Wajiga{0} Maktabadu waxay u ogolaataa injineerada inay ka gudbaan natiijooyinka fudud ee "Pass/Fail". Marka la is barbar dhigo qaababka dheecaanka (qaabka, booska wejiga, iyo inta jeer) ee ka dhanka ah xogta ciladaha la yaqaan, nidaamku wuxuu si toos ah u aqoonsan karaa nooca cilladaha-sida soo bixitaan fiiqan ee kirishboyga, qayb macdan sabaynaysa saliidda, ama madhan daboolka adag. Tani "Nidaamka Khabiirka" ayaa si weyn u yareynaya khatarta qaladka aadanaha inta lagu jiro falanqaynta xogta goobta.

U dir sooji
U dir sooji